Power outages don’t happen often in developed countries, but they do happen. Pump stations are fed by the power grid, so when the power goes out, it also goes out for water pumping stations. And water utilities don’t like their systems losing pressure.
The usual solution is elevated storage. With elevated storage (including ground storage on a hill), unless the outage is very long, water from storage tanks will keep the system pressurized and most customers will not even notice that the pump station is down.
But there are a lot of pressure zones out there that don’t have elevated storage or an emergency connection with a higher-pressure zone that has storage or pumps with power. These dead-end zones usually have a backup gas or diesel generator, and increasingly these days, solar and batteries that will start when power is lost.
Based on that, you would think there is no problem when power is lost. Not quite. Pumps fed by backup generators don’t reach full speed instantly. First, the control system needs to detect that power is indeed off for a certain duration. Next, it needs to issue a signal to start the generator which takes a few seconds. Then the pump needs to receive a signal to start and come up to speed, and finally, a control valve may also need to slowly open. All this happens fairly quickly, but not instantaneously, meaning there will always be low or negative pressure somewhere in the pressure zone.
During the time it takes for the pump to get up to full speed, two related but different phenomena are occurring.
- The first phenomenon occurs when customers at low elevations continue to use water and leaks will persist. Why? When a customer at a lower elevation opens a faucet while customer at a higher elevation has an opens faucet, air is sucked into the system to replace the water that is flowing out.
- The second phenomenon occurs when the pump initially shuts down quickly. A low-pressure transient wave moves through the system and reduces pressure even lower than one would expect in item one above. If the negative wave is sufficiently large, I’ve even documented negative pressures occurring in a system with elevated storage.
- In systems without storage, a generator is essential, but even then, it does not provide perfect protection against low pressure.
- Since these events are short-lived, a small hydropneumatic tank can keep the system pressurized as the pumps are restarted. However, because the pumps in these zones are never shut off completely, water in the tank can get stale and lose disinfectant residual. In this case, the tank will periodically need to be drained and refilled with fresh water.
- An emergency control valve from a higher-pressure zone can be installed to bring water from that zone. In some cases, if suction pressure to the pump station is sufficiently high, water from the suction-side zone can be brought into the zone of interest through a check valve.
- The pump station can have a second power supply from a portion of the electrical grid that is somewhat independent from the main power supply. This can work when the power outage only affects the main power supply but not the secondary feed.