Home / Software Posts / How Many Isolation Valves are Enough?

How Many Isolation Valves are Enough?

Tom Walski Profile Image

Tom Walski, Ph.D, P.E, Senior Product Manager, Water

OpenFlows-WaterGEMS

Share

Isolation valves are essential components of water distribution systems. Without them, repairing a pipe break or performing other maintenance would require shutting down the entire water distribution system or resorting to some heroic work on pressurized pipes.

But how many isolation valves are needed? They are not inexpensive, and they require occasional maintenance. Installing too many valves can be a waste of money, while too few valves result in an unreliable system with frequent service interruptions. Ideally isolation valves in a distribution system would enable a shutdown to be isolated to a single city block.

In the US, the ā€œcorrectā€ number of valves is given in Ten State Standards (GLUMB, 1992) as:

ā€œSufficient valves shall be provided on water mains so that inconvenience and sanitary hazards will be minimized during repairs. Valves should be located at no more than 500-foot (152 m) intervals in commercial districts and at not more than one block or 800-foot (244 m) intervals in other districts. Where systems serve widely scattered customers and where future development is not expected, valve spacing shall not exceed one mile (1609 m).ā€

Because the criteria for spacing between valves is not the best way to specify valve locations and also is often ignored anyway, I was interested in finding out the ā€œoptimalā€ spacing of valves and the optimal number of valves in a system. About a decade ago, I wrote up a simple optimization based on the tradeoff between valve cost and the value of water that would not be delivered (Walski, 2011).

As with most optimization problems, I made a lot of assumptions and used ā€œtypicalā€ values for the inputs. Based on the assumptions and typical values, you need to take the results shown below with a grain of salt. Hereā€™s what the results looked like.

Hydrology-valve-spacing -cost-graph

Using that approach, the ā€œoptimalā€ spacing of isolation valves was on the order of 250 ft (80 m).

I wanted to validate this result by seeing how existing water systems in developed countries space their valves and tracked down valve and other system information for a wide range of systems. The resulting table is below showing that typical practice was reasonably close to my suggested spacing.

Hydrology-density -spacing-table

But as I mentioned earlier, valve placement based on spacing is not the best way to locate a valve.

The real action occurs at intersections. If you have four pipes meeting at an intersection, how many of those pipes should have valves. This led to classifying intersections based on whether there are N, N-1, N-2ā€¦ valves. N valves is the most reliable design, but N-1 makes it possible to do a good job isolating a problem to a single city block. A lower density of valve will enable the influence of a pipe break to spread through the system.

Hydrology-valves-at-cross

The link-node model of a distribution system is great for hydraulic calculations. However, it doesnā€™t capture the topology of the system in terms of shutdowns. Shutting down a portion of a distribution system does not shut down a link (although sometimes itā€™s not too bad). There is no such thing as an isolation valve at a junction of pipes.

Isolation valves are located along pipes. Removing a pipe link from a distribution model is not the same thing as doing a shutdown. To adequately represent a shutdown, it is necessary to think of a distribution system made up of a bunch of distribution system ā€œsegmentsā€ connected by valves. I defined a segment as the smallest portion of a distribution system that can be isolated by valves (Walski, 1993).

While the pipe network in the GIS or hydraulic model may look like this with the segments shown in different colors, displaying the segments provides more information.

Hydrology-hydraulic -model-valve-coloring

The segmentā€“valve view (below) shows segments as circles, and valves as links.

Hydrology-segment-valves

Most engineers are not familiar with the segment-valve topology, so in OpenFlows WaterGEMS, we use color coding to indicate segments as shown below. In the example, the pump station on the right side of the figure appears to be fed by three pipes in the link-node model. However, because there is not a valve at the end of P-24, a break at the green arrow will shut down the magenta segment and cut off all flow to the pump station.

Openflows-watergems-crit-test

Once segments are automatically identified, the criticality analysis in OpenFlows WaterGEMS can simulate shutting down each segment individually and determine the number of valves that must be shut to isolate a segment, the number of customers out of water, and the shortfall in water delivered. This enables the engineer or operator to identify locations where an additional valve can dramatically reduce the adverse impact of a shutdown.

The figure below shows every customer that will be out of water in each segment.

Hydraulic-customers-out-of-water-graph

In a follow up paper, we were able to automatically generate the segmentā€“valve diagram with the segment number placed and the centroid of each segment. In this figure, the segment is color coded by vulnerability (Abdel-Motaleb and Walski, 2021), where figure segment 15 is the magenta segment from the earlier graph. Every segment downstream of 15 has increasing vulnerability.

Hydraulic-model-vulnerability

Use of distribution system segments and criticality analysis in OpenFlows WaterGEMS enables the user to make more informed decisions on valve number and placement.

Abdel-Motaleb, N. and Walski, T., 2021, ā€œEvaluating Segment and Valve Importance and Vulnerability.ā€ JWRPM, 147(5), 04021020.

GLUMB (Great Lakes and Upper Mississippi River Board of State Public Health & Environmental Managers) (1992) ā€œRecommended Standards for Water Works,ā€ Albany, NY.

Walski, T.M., 1993, ā€œWater Distribution Valve Topology,ā€ Reliability Engineering and System
Safety, Vol. 42, No. 1, p. 21.

Walski, T., 2011, ā€œHow Many Isolation Valves are Needed in a Water Distribution
System?ā€, CCWI Conference, Exeter, UK.

If you want to look up past blogs, go to https://blog.bentley.com/category/hydraulics-and-hydrology/.Ā  And if you want to contact me (Tom), you can emailĀ tom.walski@bentley.com.

Want to learn more from our resident water and wastewater expert? Join the Dr. Tom Walski Newsletter today!

Relevant Tags

I often title my blogs with a question that Iā€™m very happy to try to answer. ā€œWhatā€™s the Capacity of ...

Work on the upcoming AWWA Manual on Energy (M83) is wrapping up, and Iā€™ve been working with Eric Dole, National ...

Iā€™ve read a lot of papers about water loss reduction. Two concepts that show up frequently are Minimum Nighttime Flow ...

Subscribe to The Bentley Brief

Stay ahead of the curve with the latest infrastructure news and insights.